Cold plunge
shop drawings

Swallowtail cold plunge, per architect plan dated 2026-09-25: two 10" treads (architect's third tread removed), side bench at step-2 depth, 48" footwell, square inside corners. Fully grouted, reinforced 8" CMU shell (replaces the drawn concrete walls), cast-in-place steps, bonded waterproofing, tile. Wall-face suction channel, step-riser returns, cedar roll-up cover parking on a shelf behind the suction wall.

ContractorPasadena Pools
DrawnScott / Claude
Interior4'-0" × 4'-0"
DateSep 29, 2026
ScaleAs noted
StatusFor review
Adjust dimensions (all drawings redraw)

3D overview

Drag to orbit, pinch or scroll to zoom. Cutaway removes the near wall so you can see the treads, the side bench and the footwell.

drag · zoom
8" CMU, grouted solid Tile over membrane Coping Suction channel / nosing Water

Plan

Finished interior dimensions. Walls under the coping shown dashed. Cut lines A and B key to sheet A2.

1

Floor plan

Scale ≈ 1" = 1'-0" at full width

Sections

Section A runs down the steps to the footwell toward the suction wall. Section B cuts across the footwell and side bench looking at the channel grate.

A

Section A–A · long section down the steps

Detail bubbles 1 and 2 key to sheet A3
B

Section B–B · cross section at footwell & bench

Looking at suction wall, grate in elevation

Details

Enlarged from Section A. Rebar shown is sized on sheet A5 — the engineer of record sets final sizes and spacing.

1

Suction wall at footwell

Wall, base, channel, slab, deck edge
2

Entry wall & steps

Cast-in-place treads, returns, penetration

Cedar roll-up cover

The cover rolls away from the steps and parks on the floor behind the suction wall. Slats ride on a rebated lip along both side walls so the cover sits flush with the coping.

Cover inputs
3

Cover plan · deployed and parked positions

Shelf depth is measured from the water's edge
C

Section C–C · cover rolled onto the shelf

Along the entry axis, looking toward the bench
4

Side-wall lip detail

Rebate in coping, slat flush with finished floor

CMU wall structure

A first-pass strength check of the plunge wall as a fully grouted, reinforced 8" CMU cantilever fixed at the slab, per TMS 402 strength design. Two governing cases: plunge full with nothing outside, and plunge empty with backfill against the wall. Adjust the inputs and the check updates.

Not a stamped calculation. The wall also spans horizontally to the corners, which this ignores (conservative). Soil values are assumed until the geotech or engineer confirms them.
Structural inputs
5

Wall reinforcing elevation · suction wall

Running bond, every cell grouted

Notes

Status: concept shop drawings for layout and coordination. Reinforcing, wall design and soil assumptions must be confirmed by the engineer of record, and suction outlet design by the equipment/hydraulic designer, before construction.